For African mines that rely on an on-site power station, or on a weak grid with a station as backup, those characteristics decide how many units are needed, how they are controlled and what happens when one trips. This guide sets out how each underground load behaves and what it asks of the generating plant.
Why underground loads are different
Processing loads tend to be large but steady once the mill is running. Underground loads are a mix of cyclic, continuous and emergency duty. A rock winder may accelerate a full skip every couple of minutes, ventilation fans run without pause for the life of the shaft, and dewatering pumps must restart quickly after any interruption or the lower levels begin to flood.
The station therefore has to cope with repeated load swings while protecting a base of loads that may never be shed. Planners who size the plant from an average demand figure alone tend to find frequency dips during winding and too little reserve when an engine is down for service.
Shaft winders: the cyclic load
Modern winders are usually driven by large motors through variable frequency drives or older thyristor converters. Each wind has an acceleration phase with high power draw, a constant-speed phase and a braking phase. On an isolated power station, the acceleration step is often the single biggest load change the generators see in normal operation.
Ask the winder supplier for the duty cycle: peak power, ramp profile, number of winds per hour and the behaviour during an emergency stop. That data lets the power engineer check that the engines can accept the step without unacceptable frequency or voltage dips, and whether a battery system or flywheel would smooth the swings.
Regenerative braking and the power station
When a loaded conveyance descends or a winder brakes electrically, the drive can push energy back into the network. On a grid connection this is useful. On an island network fed by reciprocating engines or gas turbines, reverse power has nowhere to go unless other loads absorb it, and generators may trip on reverse power protection.
Common answers are braking resistors on the drive, a minimum running load maintained by other consumers, or a battery energy storage system that absorbs the surplus. Agree the approach early, because it affects drive selection, protection settings and the control philosophy for the whole station.
Main and booster fans
Main ventilation fans on surface and booster fans underground are among the most important loads on the mine. They are usually continuous, sized for the deepest planned workings and often fitted with soft starters or drives. Losing them stops work underground and, in a gassy or hot mine, starts an evacuation.
Treat main fans as protected load. The station design should keep them supplied through the loss of the largest generating unit, and the load shedding scheme should drop non-essential consumers before the fans are ever at risk. Our article on critical loads that need emergency power on a mine explains how to rank these consumers.
Refrigeration and cooling at depth
Deep mines can need large refrigeration plants that chill water or air before it is sent underground. Compressor motors in these plants are big, and chiller demand rises with ambient temperature, so the hottest months bring the highest cooling load just when engine output derates in the heat.
Model the cooling demand month by month alongside site temperature and altitude. Where both peaks coincide, the station may need an additional unit or thermal storage, such as ice or chilled water held in tanks, to shift some cooling demand into cooler hours.
Dewatering pumps and recovery after a trip
Dewatering is a quiet load until it stops. Main pump stations lift water through high heads, often in several stages, and their motors may be the largest single machines underground. After a blackout, the pumps must restart in a controlled order, and the station must be able to pick them up without a second trip.
Write a restart sequence that brings fans and pumps back first, then winders, then production loads. Test it during commissioning, and repeat the test after any change to the generating fleet.
Compressed air and the remaining loads
Compressors for rock drills and services, underground substations, workshops, lighting and refuge chambers make up the rest of the underground demand. Some of these loads can be scheduled, which gives the control system room to shed or delay them when a winder accelerates or a unit trips.
Refuge chambers and communication systems need their own backed-up supplies, independent of the main station, so that a total outage never leaves people underground without air or contact.
Station sizing and unit choice
Size the plant for the coincident peak of winding, ventilation, cooling and pumping, plus processing, and then add at least one unit of spare capacity so that maintenance never eats into the protected load. Multiple medium units usually handle step loads and maintenance better than a few very large ones. The same motor-starting checks we describe for starting large mill motors apply to the largest fan and pump motors.
Where a mine expects to deepen over time, plan the station in phases. Our guide to phased HFO station expansion shows how foundations, switchgear and fuel systems can be prepared for later units.
Supply options for remote shafts
High-speed diesel sets in containers suit early development and remote ventilation shafts. Medium-speed engines on heavy fuel oil often suit a long-life mine with a high, steady base load. Gas engines or gas turbines fit where gas is available, and solar with batteries can reduce fuel burn on the surface loads while the batteries also help with winder swings.
A remote ventilation or pumping shaft some distance from the main station may justify its own small plant or a dedicated overhead line. Compare the cost and reliability of each route before deciding, and remember that a single line becomes a single point of failure for a life-safety load.
Who wrote this guide
This page comes from our mining power engineers, who plan, build and run on-site stations for mines across Africa. USP&E is the EPC and O&M contractor on those plants, never a broker, with 24+ years in the field, 150+ power projects in 45+ countries and 25,000 MW contracted since 2002. Our approach to running mine stations is set out on the operations and maintenance page.
Offices: Colorado Springs (1755 Telstar Dr, Suite 300), Knoxville (800 S Gay St, Suite 700), London (162-168 Regent Street), Johannesburg (22 Kildoon Rd, Bryanston), Cape Town (31 Brickfield Road, Woodstock) and China (No. 1 Ningzhou Road, Wuxi). Regions: USA | AFRICA | UK | UAE | CHINA. ISO 9001 and ISO 45001 certified.
Underground mine power questions
Which underground loads must never be shed?
Main ventilation fans, dewatering pumps, refuge chambers and communication systems are normally treated as protected loads. The load shedding scheme should drop production and service loads first.
Can a winder feed power back into an on-site station?
Yes. During braking or when lowering loads, a regenerative drive can return energy. On an island network this must be absorbed by braking resistors, other loads or a battery system, or generators may trip on reverse power.
How do winders affect generator sizing?
The acceleration phase of each wind is a large, repeated step load. Generators must accept it without excessive frequency or voltage dips, which often means more, smaller units or support from batteries.
Should a remote ventilation shaft have its own generators?
It can, if the distance or the reliability of a single line makes a dedicated supply safer or cheaper. Compare both options with the shaft’s life-safety role in mind.
Plan the power for your shaft
Send the winder duty cycle, fan and pump motor list and the mine plan by depth, and our engineers will build the load profile and compare supply options for each phase.
You can reach the engineering desk on +27 10 822 2324, send drawings or data sheets to info@uspeglobal.com, or leave the details on the mine power enquiry form. Generating sets that could cover early shaft sinking are listed in our diesel generator stock.